Search Our Site

Contact Us: (00353) 045 408164  (00353) 045 408165     Email: info@itsirl.com
The TT220X series consist of 2 products, one for resistance sensors and one for thermocouple sensors. They are both approved to ATEX and IECEx standards allowing for use in hazardous area applications. The TT200X series are designed for use with RTD / Slidewire, or thermocouple sensors. Other sensor characteristics or your own 22 point linearisation characteristic (for slidewire, linear resistance or mV) can be downloaded into the product enabling you to adapt it exactly to your application.

RESISTANCE RTD INPUT

Standard RTD PT100,PT500,PT1000, Cu100, Cu1000, Ni100, Ni120, Ni1000, Cu53, library

Slide wire Pot range (1 to 100) K*, Signal (0 to 100) %, accuracy 0.1 %

Resistance (10 to 500) * ± 0.055 *, (500 to 2500) * ± 0.5 *, (2500 to 10500) * ±10.0 *.

Thermal Drift (0 to 500) * 0.013 */°C,(500 to 2500) * 0.063 */°C,

(2500 to 10500) * 0.27 */°C

Excitation current < 200 uA

Lead effect Max lead resistance 20 * per leg, Effect 0.002 °C / *

OUTPUT

Type Two wire (4 to 20) mA current Loop

Range (4 to 20) mA; Upscale burnout 21.5 mA ; Downscale Burnout 3.8 mA

Accuracy (mA Out/ 2000) or 5 uA which ever is the greater, Drift 1 uA/°C

Loop Effect ± 0.2 uA/ V

Max output load TTR200 [(Vsupply-10)/20] K Ohms (Example 700 Ohms @ 24 V)

Loop Supply (10 to 30) VDC

SUPPLY

Range (10 to 30) VDC

Power < 1W Full Power

GENERAL

Accuracy 0.2°C + (°0.05% of reading) + (sensor)

Response time Start up 5 seconds, Update 160 mS, Response 500 mS, Warm up 2 minutes.

Connections Screw terminals 2.5 mm Maximum

USER INTERFACE

Type USB 2.0

Baud rate 1200 baud

Equipment PC running windows XP or later, USB configurator.

USER INTERFACE FUNCTIONS

Scaling User signal to process value scaling, for simplified setup.

Filter Adjustable time constant (0 to 100) Seconds.

User Linearisation (Profile) (2 to 22) segments mV to process.

Process Units 4 Characters (signal input only)

Temperature units °C or °F (TC inputs only)

Tag Number 20 Characters

Process Output Range in process units

User offset Enter sensor offset (Temperature mode only).

Active scaling Set output process range against active sensor input

ENVIRONMENT

Operating Ambient TTR200(-40 to 85) °C ; (10 to 90) %RH (non condensing)

TTR200X Refer to user manual

Storage Ambient (-50 to 90) °C; (10 to 90) %RH (non condensing)

Configuration Ambient (10 to 30) °C

Installation Enclosure >= IP65.

APPROVALS

CE BS EN 61326

MECHANICAL

Style Head mounted terminal block

Diameter 43 mm diameter; 21 mm height Weight 31 g (encapsulated)

SENSORS RTD

Platinum IEC Pt100 (-200 to 850), Pt500 (-200 to 750), Pt1000 (-200 to 600)

Platinum IPTS-68 Pt100 (0.00391) + Pt100 (0.00392) (-200 to 630)

Ni100 DIN 0.00618 (-60 to 180) Ni120 0.00672 (-80 to 260)

Ni 1000 (-60 to 180) Ni1000 Tk5000 (-50 to 150)

Ni 507.5 (-80 to 360) Ni 604 (-200 to 200)

Cu 53 (-50 to 180) Cu100 0.00427 (-80 to 260)

Cu1000 (-80 to 260)

Silicon KTY81-110 -120-121-122-150-210-220-221-222-250 (-55 to 175)

KTY82-110 -120-121-122-150-210-220-221-222-250 (-55 to 175)

KTY81-151,KTY82-151, KTY83-210-220-250-121-122 (-55 to 175)

KTY84-130-150 (-40 to 300)

Datasheet

Get in Touch

Unit W4A
Ladytown Business Park
Naas
Co. Kildare
Ireland.
W91 XEX5

(00353) 045 408164