Calibratable outdoor humidity ⁄ temperature sensor (± 3 %) or (± 2 %)

It converts the measured humidity and temperature into a standard signal of 0 - 10 V or 4...20 mA, and is available with ⁄ without an optional display. It is equipped with four switchable temperature ranges. Relative humidity (in % r. H.) is the quotient of water vapour partial pressure pided by the saturation vapour pressure at the respective gas temperature.
It is used in non-aggressive, dust-free environments, in the refrigeration, air conditioning and clean room technology, hotels, engineering rooms, meeting and conference facilities. The measuring transducers are designed for exact detection of temperature and humidity. A digital, long-term stable sensor is used as a measuring element for humidity and temperature measurement. Fine adjustment by the user is possible. The sensor is suitable for ceiling and duct installation or for integration in equipment.
Humidity: 0...100% r.H.,
Temperature: -35°C...+80°C
Output: 0-10V or 4...20mA
metal sinter filter

Voltage supply 15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Power consumption < 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
Working resistance Ra (ohm) = (Ub -14 V) ⁄ 0.02 A for I variant
Sensors digital humidity sensor
with integrated temperature sensor,

low hysteresis, high long-term stability
Measuring range, humidity 0...100 % r. H.
(output corresponding to 4...20 mA)
Operating range, humidity 0...95 % r. H. (without dew formation)
Deviation of humidity typical ± 1,8 % r. H. (10…90 % r. H. ); at + 25 °C, otherwise ± 2 % r. H.
Output, humidity 4...20 mA
Sensor protection pluggable measuring head (probe) with
metal sinter filter, Ø 16 mm, L = 88.5 mm, exchangeable
Ambient temperature storage –35...+85 °C
operation –30...+70 °C
Protective tube stainless steel, Ø = 18 mm (16 mm), L = 120 mm
Electrical connection 2-, 3- or 4-wire connection
0.14 -1.5 mm ² via terminal screws on circuit board
Enclosure plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted ⁄ Phillips head - combination),
colour traffic white (similar to RAL 9016),
enclosure cover for display is transparent !
Enclosure dimensions 126 x 90 x 50 mm (Tyr 2)
Cable gland 2x M 12 x 1.5 (Y-adapter); with strain relief,
exchangeable, max. inner diameter 6 mm
Connection cable KL = 2 m
Long-term stability ± 1 % ⁄ year
Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529)
Standards CE conformity,
according to EMC directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
Display three-line display with illumination, cutout 70 x 40 mm (W x H),
for displaying ACTUAL temperature and ⁄ or ACTUAL humidity