Calibratable outdoor humidity ⁄ temperature sensor (± 3 %) or (± 2 %)
with plastic sinter filter (optional metal sinter filter) or with pluggable metal sinter filter; terminal box enclosure made of impact-resistant plastic, with ⁄ without optional display.
It measures the relative humidity and ⁄ or the temperature of the air and converts the measured into a standard signal of 0 - 10 V or 4...20 mA um. It has four switchable temperature ranges and is applied in non-aggressive dust-free atmospheres in refrigeration, air conditioning, ventilation and clean room technology. Relative humidity (in % r. H.) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature. These measuring transducers are designed for exact detection of humidity. A digital long-term stable sensor is used as measuring element for humidity measurement. Fine adjustment by the user is possible.
Humidity: 0...100% r.H.,
Temperature: -35°C...+80°C
Output: 0-10V or 4...20mA
Voltage supply | 15...36 V DC depending on working resistance, residual ripple stabilised ± 0.3 V |
---|---|
Power consumption | < 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC |
Working resistance | Ra (ohm) = (Ub -14 V) ⁄ 0.02 A for I variant |
Sensors | digital humidity sensor with integrated temperature sensor, low hysteresis, high long-term stability |
Measuring range, humidity | 0...100 % r. H. (output corresponding to 4...20 mA) |
Deviation of humidity | typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 % r. H. |
Output, humidity | 4...20 mA |
Measuring range, temperature | multi-range switching –35...+35 °C; –35...+75 °C; 0...+50 °C; 0...+80 °C (output corresponding to 0 -10 V or 4 … 20 mA) |
Temperature deviation | ± 0.2 K at +25 °C |
Output, temperature | {Reference (Object) not found: prod7604333337944} |
Sensor protection | plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable (optional metal sinter filter, Ø 16 mm, L = 32 mm) |
Ambient temperature | storage –35...+85 °C; operation – 30...+80 °C, non-precipitating |
Process connection | by screws |
Protective tube | stainless steel, Ø 16 mm, NL = 55 mm |
Electrical connection | 2-, 3- or 4-wire connection 0.14 -1.5 mm ² via terminal screws on circuit board |
Enclosure | plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted ⁄ Phillips head - combination), colour traffic white (similar to RAL 9016), enclosure cover for display is transparent ! |
Enclosure dimensions | 126 x 90 x 50 mm (Tyr 2) |
Cable gland | 2x M 12 x 1.5 (Y-adapter); with strain relief, exchangeable, max. inner diameter 6 mm |
Long-term stability | ± 1 % ⁄ year |
Permissible air humidity | < 95 % r. H., non-precipitating air |
Protection class | III (according to EN 60 730) |
Protection type | IP 65 (according to EN 60 529) enclosure only! |
Standards | CE conformity, according to EMC directive 2014 ⁄ 30 ⁄ EU, according to EN 61326-1, according to EN 61326-2-3 |
Display | three-line display with illumination, cutout 70 x 40 mm (W x H), for displaying ACTUAL temperature and ⁄ or ACTUAL humidity |