The calibratable humidity and temperature sensor measures the relative humidity and ⁄ or the temperature of the air
It converts the measured humidity and temperature into a standard signal of 0 - 10 V or 4...20 mA, and is available with or without an optional display (for displaying actual humidity and actual temperature), in an elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment for installation on vertically or horizontally installed in-wall flush boxes, with predetermined breaking point for on-wall cable entry, or in an enclosure made of stainless steel (top and bottom part are of stainless steel, the lid is screwed on), vandal-proof version e.g. for schools, military barracks, and public buildings.
It is used in non-aggressive, dust-free environments, in refrigeration, air conditioning and clean room technology, in interior rooms, such as living rooms, offices, hotels, engineering rooms, meeting and conference facilities. The measuring transducers are designed for exact detection of temperature and humidity. A digital, long-term stable sensor is used as a measuring element for humidity and temperature measurement. Fine adjustment by the user is possible.
Voltage supply | 15...36 V DC depending on working resistance, residual ripple stabilised ± 0.3 V |
---|---|
Power consumption | < 1,0 VA ⁄ 24 V DC < 2,2 VA ⁄ 24 V AC |
Working resistance | Ra (ohm) = (Ub -14 V) ⁄ 0.02 A for I variant |
Sensors | digital humidity sensor with integrated temperature sensor, low hysteresis, high long-term stability |
Measuring range, humidity | 0...100 % r. H. (output corresponding to 4...20 mA) |
Operating range, humidity | 0...95 % r. H. (without dew formation) |
Deviation of humidity | typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 % r. H. |
Output, humidity | 4...20 mA, working resistance < 800 Ω |
Measuring range, temperature | 0...+ 50 °C (output corresponding to 0 -10 V or 4... 20 mA or Ohm value) others upon request! |
Operating range, temperature | 0...+50 °C |
Temperature deviation | ± 0.2 K at +25 °C |
Output, temperature | 4...20 mA |
Ambient temperature | storage –25...+50 °C, operation –5...+55 °C |
Electrical connection | 2-, 3- or 4-wire connection 0.14 -1.5 mm ² via terminal screws on circuit board |
Enclosure | plastic, material ABS, colour pure white (similar to RAL 9010) |
Dimensions | 85 x 85 x 27 mm (Baldur 1) |
Installation | wall mounting or on in-wall flush box, Ø 55 mm, base with 4 holes, for attachment to vertically or horizontally installed in-wall flush boxes for rear cable entry, with predetermined breaking point for cable entry from top ⁄ bottom in case of plain on-wall installation |
Long-term stability | ± 1 % ⁄ year |
Protection class | III (according to EN 60 730) |
Protection type | IP 30 (according to EN 60 529) |
Standards | CE conformity, according to EMC directive 2014 ⁄ 30 ⁄ EU, according to EN 61326-1, according to EN 61326-2-3 |
Display | two-line display with illumination, 36 x15 mm (W x H), for displaying ACTUAL temperature and ⁄ or ACTUAL humidity |