INPUT
RH range (0 to 100) %RH RH accuracy +/- 4 %RH between (10 to 90)%RH
Temperature range (-30 to 100) °C Temperature accuracy +/- 0.5 °C between (-20 to 80)°C
Dew point range (0 to 50) °C
Delta temperature (Delta T)= Ambient temperature – dew point temperature Delta T range (0 to 50) °C
Thermistor Optional discrete thermistor to replace second (4 to 20) mA channel.
Thermistor to be read directly by user. Single channel version only.
10 K NTC, data on request.
CH1 (CH2) OUTPUTS
Output type 2 wire (4 to 20) mA current loop
Output range (4.0 to 20.0) mA
Output connection Two part screw terminal
Maximum output > 20.5 mA in high burnout condition
Minimum output < 3.9 mA in low burnout condition
Accuracy (mA output /2000) or 5 uA, whichever is the greater
Loop voltage effect 0.2 uA / V
Thermal drift 1 uA / °C
Maximum output load [(Vsupply-10)/20] K Ohms (Example: 700 Ohms @ 24V)
Channel isolation 500 Vdc
Switch settings CH2 only Four switch selected ranges provided
Note CH1 = main supply channel and must be powered, CH2 acts as slave to CH1
GENERAL SPECIFICATION
Update time 3 Seconds
Start-up time < 10 seconds, I out < 4 mA during start up
Power Supply (10 to 30) Volts dc
Operating temperature
Electronics housing (-20 to 70) °C
Probe (-30 to 100) °C
Datasheet