The Multicon CMC-99 is a powerful and versatile compact-multichannel-controller with a capability to record data, if the recording function is requested and activated. Thanks to that it is one of the first industrial devices which integrates advanced control functions (PID, ON/OFF, time & profiles etc.) and logging of setpoints, excitations and current state of controlled objects. Based on Linux firmware, is stable and the touch screen makes configuration easy and comfortable and data presentation also readable and attractive. Although the Multicon CMC-99 is build in a quite small housing, it can integrate up to 48 inputs, and its construction allows user almost free configuration by choosing up to 3 from 16 available input/output modules.

Storage temperature -10°C ÷ +70°C or -20°C ÷ +70°C (depending on version)
Operating temperature 0°C ÷ +50°C (standard), -20°C ÷ +50°C (option)
Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Input 9 universal inputs max.; 48 analogue inputs (0/4-20 mA or 0/1-5V or 0/2-10V) max.; 48 digital inputs max.; 24 thermocouple inputs max.; 12 RTD inputs max.; 12 counter/ flowmeter/ ratemeter inputs max.; 1 digital input 24V DC (available in standard, integrated with PS3 or PS4 power supply module)
Power consumption typical 15 VA; max. 20 VA
Case material NORYL - GFN2S E1
Protection class IP 65 (front), available options: additional frame IP 65 for panel cut-out sealing, transparent door STD-99; version with front USB: IP 40 or IP 54 (when fitted with STD-99 transparent door)
Display 3.5 inch graphic TFT, 16-bit colour, 320 x 240 pixels, with touchscreen
Measurement range depends on input
Communication interface standard: RS-485 (Modbus RTU), 1 x USB Host; ETU version: 1 or 2 x USB Host, 1 x Ethernet 10 MB; enhanced ACM version: 2 x RS-485, 1 x RS-485/232, 1 or 2 x USB Host, 1 x Ethernet 10 MB
Output 8 analog (4-20 mA) max.; 16 relay (1A/250V) max.; 4 relay 5A/250V max. or 48 SSR outputs, sensor supply: 24 V DC ± 5% (200 mA max. for current inputs)
Internal memory capacity internal 1,5 GB
Case panel mounting
Available data recording speed from 0,1 s to 24 h with resolution 0,1 s
Case dimensions 96 x 96 x 100 mm
Panel cut-out dimensions 90,5 x 90,5 mm
Software Free DAQ Manager software for multichannel controller can be downloaded directly from section „Download”
Installation depth min. 102 mm